Products
  • Products
  • Suppliers
  • Categories

Air Cooled Chiller (Close Type)

Product ID: AU-3RT, AU-5RT, AU-8RT, AU-10RT, AU-12RT, AU-15RT

Send Inquiry
Features
  • Microprocesser Automated Control System:
    • We make high precision temperature of come true even to 1°C difference that will insure your product quality uniformly.
  • Easy-to-Watch Control Panel:
    • You may look after temperature indicating, temperature control, operating condition, alarming and easy-to operate through a well-seeming panel.
  • Fully Automatic Power Saving Control System:
    • Unique owned special program can start up step by step until to whole functions work stably. Once the set temperature reaches, the chiller will also stop with step by step to save energy.
  • High Efficient Components and Most Safe Protections:
    • Equipped with high efficient compressor imported from Europe America or Japan. Chiller can work perfectly by mean of complete series of elements such as Electronic control instrumentation, high/low pressure protector, Drier/Filter of refrigerant and overload relay.
  • Super High Efficiency Heat Exchanger:
    • Using the latest SUS316 condenser, copper pipe C1220 screw type evaporator.
  • Typical Components
    • Electronic Thermocouple
    • High Pressure Gauge
    • Low Pressure Gauge
    • Dryer/Filter
  • Safety System
    • Overload of Compressor
    • Overload of Pump
    • High/Low Pressure Gauge
    • Signal Lamp
    • Float Switch
    • Buzzer
  • Options
    • Pressure Gauge
    • Three Way Valv
    • Cryostat
    • Corrosion - Resisted Heat Exchanger
  • Cooling capacity based on ambient temp. +35°C, Chilled water inlet temp. at +12°C and Outlet temp. at +7°C.
  • Cooling water quantity about 12L/mil per 1200 Btu/Hr. needed.
  • Don't put the heat to be removed over the cooling capacity. i.e. [Heat to be removed x 1.25 = cooling capacity]. To ensure the chiller is used under normal condition.
  • In case of using in 50Hz area, then cooling capacity becomes as (60Hz) x 0.83 = (50Hz).
Model Unit AU-3RT AU-5RT AU-8RT AU-10RT AU-12RT AU-15RT
Temp. Range °C +5°C / 30°C +5°C / 30°C +5°C / 30°C +5°C / 30°C +5°C / 30°C +5°C / 30°C
Cooling Capacity But/Hr 36000 60000 90000 120000 140000 180000
Kcal/Hr 9072 14600 23000 30240 35260 45340
Kw 10.5 17.5 28 35 40 52
Power Consumption Kw 5 7.5 12 15.4 17.3 20.7
Power Source & Operating Current 1Dia.220V60Hz/A 22 33
3Dia.220V60Hz/A 15 19 34 40 45 54
3Dia.380V60Hz/A 8 12 18 22 25 28
Compressor Type MT-36 MT-56 MT-80 MT-100 MT-125 MT-160
Power - kw 2.2 3.8 6 7.5 8.1 12
Fan Type Axial Fan Axial Fan Axial Fan Axial Fan Axial Fan Axial Fan
Power - kw 0.24 0.24 0.24 x 2 0.24 x 2 0.35 x 2 0.35 x 2
Pump Type Coaxial Volute Pump Coaxial Volute Pump Coaxial Volute Pump Coaxial Volute Pump Coaxial Volute Pump Coaxial Volute Pump
Power - kw 0.38 0.38 0.75 0.75 1.13 1.13
Water Flow - L/min 54 90 145 180 225 270
Water Head - M 3 ~ 12 3 ~ 12 3 ~ 12 3 ~ 12 3 ~ 12 3 ~ 12
Condenser K70 x 34C K105 x 34C K105 x 40C / K205 x 30C K105 x 40C / K205 x 30C K205 x 34C K205 x 34C
Evaporator Double Tubt Condenser Double Tubt Condenser Double Tubt Condenser Double Tubt Condenser Double Tubt Condenser Double Tubt Condenser
Refrigerant R-22 R-22 R-22 R-22 R-22 R-22
Outside Dimensions H (mm) 1250 1250 1800 1820 1820 1820
W (mm) 465 465 580 580 580 580
D (mm) 950 1060 900 900 1350 1350
Wheel C 100 100 100 100 100 100
Chilling Water Pipe inch 1" 1" 1 1/4" 1 1/2" 2" 2"
Power Soure Wire mm 2.0 x 4C 3.5 x 4C 5.5 x 4C 8.0 x 4C 14.0 x 4C 14.0 x 4C
Weight Kg 160 180 210 250 310 360

Main Products